These Lead Results are in parts per billion (ppb). For reference, 1 ppb would be 1 part of lead for every billion parts of water (roughly one drop of water in an olympic-sized swimming pool). If the result is 0.5 ppb, this means the lab could not detect lead in the sample.
The results in red were above our remediation threshold. Finding lead sources takes time and can be complicated. You can see what remediation measures were taken in the Remediation column.
Check out the CDC's website to learn more about lead in drinking water.
Fixture Code | Fixture Type | Fixture Location | Lead Result | Remediation Action | Collection Date | |
|---|---|---|---|---|---|---|
| DEMO2222 | Faucet, Cold | visitor concession NE Make: Central Brass | 8.60 ppb | -- | 2019-6-11 | |
| DEMO2237 | Faucet, Cold | athletic office | 2.70 ppb | -- | 2019-6-11 | |
| DEMO2211 | Faucet, Cold | room c 236 opposite side | 2 ppb | -- | 2019-6-11 | |
| DEMO2261 | Water Cooler | Cafeteria west end next to serving | 3.60 ppb | -- | 2019-6-11 | |
| DEMO2281 | Drinking Water Fountain | home concession NW | 0.50 ppb | -- | 2019-5-2 | |
| DEMO2282 | Drinking Water Fountain | ouside home concession NW | 0.50 ppb | -- | 2019-5-2 | |
| DEMO2233 | Faucet, Cold | Northwest concession Home | 0.50 ppb | -- | 2019-5-2 | |
| DEMO2283 | Drinking Water Fountain | varsity locker room west | 0.50 ppb | -- | 2019-5-2 | |
| DEMO2223 | Other | Training room | 2.90 ppb | -- | 2019-5-2 | |
| DEMO2307 | Ice Machine | trainer room | 0.50 ppb | -- | 2019-5-2 | |